Quick answer

Under BS 5266-1, emergency lighting must be tested every month with a short functional test, and once a year with a full-duration test (usually 3 hours). Every test, fault and repair must be written in an emergency lighting logbook. In England and Wales, the “responsible person” for the building is legally accountable for making sure this happens under the Regulatory Reform (Fire Safety) Order 2005.

Emergency lighting is easy to forget about because, most of the time, it does nothing. But if the power fails during a fire, those fittings are what get people down the stairs and out of the building. This guide explains exactly what testing is required, how to do the monthly test yourself, and when you need a competent engineer.

Monthly

A short functional test of every light and sign.

Every year

A full 3-hour duration test by a competent person.

Every test

Recorded in the emergency lighting logbook.

How often should emergency lighting be tested?

TestHow oftenWhat it involvesWho can do it
Daily visual checkDaily (where there is a central battery system)Check indicator lights show the system is healthyTrained member of staff
Monthly functional testEvery monthSimulate a mains failure briefly and check every light and sign comes onTrained member of staff
Annual full-duration testEvery 12 monthsRun all fittings on battery for their full rated duration (normally 3 hours) and check they stay litCompetent person, usually an engineer

How do you do a monthly emergency lighting test?

The monthly “flick test” is quick and can be done by a trained member of staff:

1

Locate the test key switch for each emergency lighting circuit. These are usually small key switches near the distribution board or light switches.

2

Turn the key to cut the mains supply to the fittings. This simulates a power cut without switching off the rest of the building.

3

Walk the building and check every emergency light and illuminated exit sign is lit.

4

Keep the test short. A few seconds is enough, and it shouldn’t drain the batteries.

5

Restore the supply and check the charging indicators (normally a small green LED) are back on.

6

Record the date, result and any faults in the logbook, then arrange repairs for anything that failed.

Alarm Installation

What is an annual emergency lighting test?

Once a year, every fitting must be tested for its full rated duration, which is 3 hours for most premises. Some buildings that are evacuated immediately and not reoccupied may use 1-hour fittings, but 3 hours is the norm and is required anywhere people sleep or may need to stay after the power fails, such as care homes, hotels and blocks of flats.

After a full-duration test, the batteries take up to 24 hours to recharge. During that time the building has reduced emergency lighting cover, so the test should be done when the building is empty or lightly occupied, or carried out in stages so that neighbouring fittings are not all discharged at once. This is one reason most businesses ask an engineer to do the annual test as part of their servicing and maintenance visit.

What should an emergency lighting logbook include?

Fire officers, insurers and auditors will ask to see your logbook. It should record:

If you can’t show a fire officer a logbook, they have no way of knowing your system has been tested, and you may be treated as non-compliant even if the lights work.

Who is responsible for emergency lighting testing?

The “responsible person” under the Fire Safety Order. In a business this is usually the employer, owner or managing agent. In the communal areas of flats and HMOs it is normally the landlord, freeholder or managing agent. You can delegate the testing itself, but not the legal responsibility. Failing to maintain emergency lighting can lead to enforcement notices, fines and, in serious cases, prosecution.

Are self-testing emergency lights worth it?

For many buildings, yes. Self-test (automatic test) fittings carry out their own monthly and annual tests and show a status light or report to a central panel. They save staff time and remove the risk of tests being forgotten. You still need to check the results, record them in the logbook and have the system inspected by a competent person. They are a good option for large sites, multi-site businesses and buildings without a dedicated facilities manager.

What are common emergency lighting faults?

Frequently asked questions

Is emergency lighting testing a legal requirement?

Yes. The Regulatory Reform (Fire Safety) Order 2005 requires emergency lighting to be maintained in efficient working order. BS 5266-1 is the recognised standard for how to do that, including monthly and annual testing.

How long should emergency lights stay on during a power cut?

Usually 3 hours. A 1-hour duration is only acceptable in certain premises where the building is evacuated straight away and not reoccupied until the supply is restored.

Can I do the emergency lighting test myself?

You can do the monthly functional test yourself once you’ve been shown how. The annual full-duration test and periodic inspection should be done by a competent person who can check the whole system against BS 5266-1 and issue a certificate.

Do homes need emergency lighting?

Individual houses don’t normally need it. The communal areas of flats and many HMOs do, depending on the building’s size, layout and fire risk assessment. Read our guide to domestic fire and emergency lights for more.

How much does an emergency lighting test cost?

It depends on the number of fittings and whether the annual test is combined with your fire alarm service. Combining them in one visit is usually the most cost-effective option. Contact us for a quote based on your building.

Emergency lighting testing in Kent

Watchman Fire & Security installs and maintains emergency lighting and signage to BS 5266 for businesses, schools, care providers and landlords across Kent. Our engineers carry out annual full-duration tests, repair failed fittings, update your logbook and can combine the visit with your fire alarm service. Get in touch to book a test or a free survey.

1 Comment

HMO Fire Alarm Requirements: Landlord Guide (Kent) | Watchman
6 Nov, 2026

[…] Emergency lighting in communal areas: test monthly and do a full-duration test once a year. See our guide to emergency lighting testing. […]